Electrical engineering
Electrical cable: calculating cross-section from voltage drop
Calculate the theoretical conductor cross-sectional area for a target voltage drop using a model that neglects reactance. Choose single-phase or balanced three-phase and enter current, one-way length, voltage, cos φ and resistivity at the temperature studied.
Electrical cable: calculating cross-section from voltage drop
Reference voltage: across the single-phase circuit, or phase-to-phase for balanced three-phase.
RMS line current, strictly positive, corresponding to the load studied.
Positive one-way cable length; do not double the distance for single-phase.
Load power factor cos φ, greater than 0 and at most 1. The contribution of reactance remains neglected.
Enter 3 for 3 %. Project target to justify, with no automatic prescription.
Hypothetical example value. Use the resistivity appropriate for the conductor and its temperature.
Initial values are examples.
Results
Reactance is explicitly neglected.
Applied formulas
Values are substituted in SI units and results are shown in the selected units.
Estimated reading time : 5 min · 815 words
Calculation details
A is a continuous mathematical cross-sectional area, without rounding to an available size. dU is your target in % expressed in volts, not a drop recalculated for a commercial cable.
02 · Target voltage drop in volts
A theoretical cross-section for a target drop
Increasing the cross-section reduces conductor resistance and the resistive contribution to voltage drop. The calculation reverses this relation to find the cross-section corresponding to the given target. The calculated value is continuous; it is not rounded to a commercial size and does not constitute a complete cable selection.
Formulas and symbols
Quantities are converted to consistent units before calculation.
(continuous theoretical cross-section)
(target drop in volts)
(continuous theoretical cross-section)
(target drop in volts)
- A: theoretical cross-sectional area in , converted to for display.
- rho: conductor resistivity ρ at the temperature studied, in Ω·m after conversion; the usual input is .
- L: one-way length in m.
- I: current in A.
- c: cos φ, greater than 0 and at most 1.
- U: reference voltage in V.
- d: target drop in percent, for example 3 for 3 %.
- dU: corresponding target drop in V. The circuit factor is 2 for single-phase and for balanced three-phase.
What the theoretical cross-section covers
| Criterion | In this calculation | To check next |
|---|---|---|
| Target resistive drop | Yes, continuous model | Recalculate with the actual cable |
| Reactance X′ | Neglected | Contribution if significant |
| Commercial cross-section | No rounding | Availability and justified selection |
| Current-carrying capacity and protection | No | Installation method, temperature, short circuit and protection devices |
| Calculation temperature | Only through supplied ρ | Resistivity consistent with conductor |
Schneider Electric — voltage drop in steady-state operation ; NIST — Guide to the SI, Appendix B.9.
Worked examples
Example 1: 20 A over 40 m in single-phase
With , , target 3 % and , the target drop is 6,9 V and the theoretical area is about . It must still be compared with available sizes and other criteria.
Example 2: 63 A over 100 m in three-phase
With , , target 4 % and the same hypothetical resistivity, the target drop is 16 V. The theoretical resistive cross-sectional area is about .
Example 3: Check case
; ; ; ; ; % : ΔU = 3,45 V ; .
Example 4: 32 A three-phase supply over 60 m with an allowable voltage drop of 3 %
The theoretical minimum cross-section reaches for a voltage drop of 12 V. Select the next larger standard cross-section, , then check the cable’s current-carrying capacity for its installation method.
/ ΔU = .
Assumptions and limitations
Reactance is explicitly neglected. This model may underestimate the required cross-section when the reactive contribution is significant; then a model including X′ is needed. Resistivity and target drop are project inputs. No automatic correction for temperature, commercial size, current-carrying capacity, short circuit, protection or installation conditions.
Common mistakes
Doubling the one-way length counts the return twice in single-phase circuits: check the input convention.
Using resistivity at another temperature shifts the resistance: specify the value used.
Ignoring significant reactance underestimates voltage drop: examine the cable data.
Automatically rounding down to a smaller cross-section may miss the target: recalculate with the chosen cross-section.
Concluding compliance from this result alone omits other criteria: continue the full sizing process.
Frequently asked questions
How should the maximum voltage drop be chosen?
It must come from the requirements applicable to the project, equipment and installation. The percentages in the examples are not local prescriptions.
Why also check current-carrying capacity?
The calculated cross-section meets only the resistive criterion under the entered assumptions. Current-carrying capacity also depends on the cable and its installation method. After selecting an available size, recalculate the drop with the actual cable data and then examine the other installation criteria.
Why is no commercial size selected?
A continuous single-criterion result is not a cable selection. Recalculate with the chosen cable and check other requirements.
What if the target voltage drop is halved?
With all other data fixed, theoretical area doubles in the resistive model.