Electrical engineering
Voltage drop: calculation for single-phase and balanced three-phase circuits
Estimate the voltage drop and receiving-end voltage of a single-phase or balanced three-phase line. Enter the current, one-way length, R′ and X′, then cos φ and the inductive or capacitive nature of the load.
Voltage drop: calculation for single-phase and balanced three-phase circuits
RMS voltage at the start of the line: across the single-phase circuit terminals or between phases in a balanced three-phase system.
RMS current flowing in a line conductor at the operating point studied.
Distance from the start to the load, without adding the return path; the circuit factor is already applied.
Value at the temperature studied; fictitious example to be replaced.
Inductive reactance per unit cable length at the frequency studied. Check Ω/km or Ω/m.
Load cos φ, as a strictly positive fraction no greater than 1. Select the inductive or capacitive sign separately.
Choose +1 for a lagging current, −1 for a leading current.
Initial values are examples.
Results
Sinusoidal steady-state approximation, with identical outgoing and return conductors in single-phase circuits and a balanced circuit in three-phase operation.
Applied formulas
Values are substituted in SI units and results are shown in the selected units.
Estimated reading time : 6 min · 1173 words
Calculation details
A positive drop reduces the estimated receiving-end voltage. A negative drop describes a rise in this approximation. The percentage is calculated relative to the entered voltage U.
02 · Relative drop (in %)
03 · Estimated receiving-end voltage
Voltage drop along the line
Current creates a voltage difference along a line with resistance and reactance. The model projects this difference onto the reference voltage. In single-phase circuits, the factor 2 accounts for the two conductors of equal length and identical characteristics. In balanced three-phase circuits, the factor relates the drop per conductor to the line-to-line voltage. The R′ and X′ data describe the actual cable, its temperature and the frequency.
Formulas and symbols
Quantities are converted to consistent units before calculation.
(signed voltage drop)
(relative drop (in %))
(estimated receiving-end voltage)
(signed voltage drop)
(relative drop (in %))
(estimated receiving-end voltage)
- U: reference voltage in V, across the terminals in single-phase circuits or between phases in three-phase circuits.
- I: line current in A.
- L: one-way length in m.
- Rp and Xp: resistance R′ and inductive reactance X′ per unit length, in after conversion.
- c: cos φ.
- sign: +1 for lagging current, −1 for leading current.
- dU: signed drop in V.
- d: relative drop in %.
- Ur: estimated voltage at the end.
Circuit conventions
| Circuit | Factor | Voltage U | Length L |
|---|---|---|---|
| Single-phase | 2 | At the start of the line, between the two conductors of the circuit | One-way |
| Balanced three-phase | Between phases | One-way | |
| R′ or X′ conversion | Without changing the circuit | Same unit as R′ and X′ after conversion |
Schneider Electric — voltage drop in steady-state operation.
Plain copper, classes 1 and 2: maximum resistance at 20 °C
| Nominal conductor cross-section | Maximum DC resistance |
|---|---|
| 12,1 | |
| 7,41 | |
| 4,61 | |
| 3,08 | |
| 1,83 | |
| 1,15 | |
| 0,727 | |
| 0,524 |
Values for plain copper conductors of classes 1 and 2 according to EN/IEC 60228, reproduced in the manufacturer Bayka’s table. They do not apply directly to classes 5 and 6 or to tinned copper. Resistance at operating temperature and alternating-current effects must be established for the line under study. Bayka — Conductor resistance at 20 °C according to EN/IEC 60228, by material and class.
Line data conversions
| Initial value | Equivalent value |
|---|---|
| 1 km | 1 000 m |
| 1 kV | 1 000 V |
| 1 A | 1 000 mA |
Worked examples
Example 1: 230 V, 16 A, 30 m one way
With R′ = , X′ = and , the drop is 7,104 V, or approximately 3,09 %. The estimated receiving-end voltage is 222,896 V.
Example 2: 400 V, 50 A, 80 m one way
With R′ = , X′ = and inductive , the drop is approximately 11,48 V, or 2,87 %. The estimated receiving-end voltage is 388,52 V.
Example 3: Capacitive sign in a theoretical example
At 230 V with 10 A, 10 m, R′ = , X′ = and capacitive , the drop is −0,08 V. The model predicts a very slight voltage rise.
Example 4: 20 A construction-site socket at 45 m, with a cable
With the parameters in this example, the voltage drop reaches 12,1 V, or 5,2 % of 230 V, and the voltage at the end of the line is approximately 218 V. For comparison, the Schneider Electric guide gives reference limits of 3 % for lighting and 5 % for other uses in an installation supplied by the public low-voltage network. These concern the total drop from the installation’s origin to the point of use in steady operation; applicable limits depend on the country and installation. Increasing the cross-section or reducing the length lowers the calculated drop.
ΔU = 2 I L (R′ cos φ + X′ sin φ) = 12,1 V ; ΔU / %.
Assumptions and limitations
Sinusoidal steady-state approximation, with identical outgoing and return conductors in single-phase circuits and a balanced circuit in three-phase operation. R′ and X′ must come from data suitable for the cable; no cross-section, temperature or material is inferred automatically. The receiving-end voltage must remain positive in this model. Transients, harmonics, imbalance and regulatory criteria are not checked.
Common mistakes
Enter only the one-way length: the circuit factor is already included. Do not confuse and . Use the line-to-line voltage for three-phase circuits. A negative drop indicates a voltage rise in the capacitive approximation; the sign must not be removed.
Frequently asked questions
Should the round-trip length be entered?
No. Enter the one-way route length. The factor 2 in single-phase mode already accounts for the return through an identical conductor.
Is voltage drop enough to validate the cable?
Voltage drop is one of several criteria. The calculation does not assess current-carrying capacity, installation conditions, protective devices or short-circuit withstand. It provides a voltage estimate using the entered R′ and X′ without selecting a cable or a regulatory threshold.
Where is the reference voltage defined?
The reference voltage is at the sending end of the line. In single phase it is between the two circuit conductors; in balanced three phase it is between phases. Percentage drop uses this voltage, and receiving voltage subtracts the signed drop.
Does a negative drop mean an error?
Not necessarily. With a capacitive load, the reactive term changes sign and may exceed the resistive term, so the model predicts a small voltage rise. Check the input data and chosen sign. A large rise requires an appropriate network analysis.