Skip to content
Formulaxis

Electrical engineering

Three-phase power: calculating line current and P, Q, S

Find current and total powers for a balanced three-phase load in sinusoidal operation. Choose current, active power or apparent power as the known input, then enter line-to-line voltage, cos φ and whether the load is inductive or capacitive.

Created on , Revised on v2.0

Method and validation

Three-phase power: calculating line current and P, Q, S

Value source

RMS voltage between two phases, for example 400 V on a 230/400 V supply; do not enter the phase-to-neutral voltage.

RMS current in a supply line; do not enter an internal winding current.

dimensionless

Cosine of the phase angle, strictly positive and at most 1: enter 0,85 for 0,85, not an angle or percentage.

dimensionless

Choose +1 for a lagging current, −1 for a leading current.

Initial values are examples.

Results

Current drawn I
20A
Active power P
11.78kW
Signed reactive power Q
7.299kvar
Apparent power S
13.86kVA

Substitution in SI units

I=3×(400 V)×(20 A)3×(400 V)=20 A

Balanced three-phase load; an unbalanced load requires a calculation for each phase.

Inductive power triangle

Three-phase power: calculating line current and P, Q, S · U, I and cos φ knownTriangle on a shared scale: the slope and direction of Q follow the calculated case. P is horizontal; S joins the origin to the tip of Q.Three-phase powerU = 400 V · I = 20 AP = 11.78 kWQ = 7.299 kvarS = 13.86 kVAcos φ = 0.85 · Q > 0: inductive

Triangle on a shared scale: the slope and direction of Q follow the calculated case. P is horizontal; S joins the origin to the tip of Q.

Illustrative diagram, not to scale.

Estimated reading time : 5 min · 825 words

Calculation details

The displayed powers are the totals for all three phases. Current is that in one line; Q is positive for inductive loads and negative for capacitive loads.

01 · Current drawn

FORMULA

I=3×U×I3×U

NUMERICAL SUBSTITUTION

I=3×(400 V)×(20 A)3×(400 V)

RESULT

I=20 A

02 · Active power

FORMULA

P=3×U×I×c

NUMERICAL SUBSTITUTION

P=3×(400 V)×(20 A)×0.85

RESULT

P=11.78 kW

03 · Signed reactive power

FORMULA

Q=sign×(3×U×I)×1−c2

NUMERICAL SUBSTITUTION

Q=1×(3×(400 V)×(20 A))×1−0.852

RESULT

Q=7.299 kvar

04 · Apparent power

FORMULA

S=3×U×I

NUMERICAL SUBSTITUTION

S=3×(400 V)×(20 A)

RESULT

S=13.86 kVA

Three-phase active, reactive and apparent power

Active power P is the average rate of energy absorption. Reactive power Q represents periodic energy exchanges associated with phase displacement; it is positive for inductive loads and negative for capacitive loads. Apparent power S is the product of RMS voltage and RMS current with the circuit factor. For three balanced phases, U is the line-to-line voltage and I the line current: the factor is 3.

Formulas and symbols

Quantities are converted to consistent units before calculation.

I=3×U×I3×U(current drawn)

P=3×U×I×c(active power)

Q=sign×(3×U×I)×1−c2(signed reactive power)

S=3×U×I(apparent power)

I=Pc3×U(current drawn)

P=Pc×c(active power)

Q=sign×Pc×1−c2(signed reactive power)

S=Pc(apparent power)

I=S3×U(current drawn)

P=S×c(active power)

Q=sign×S×1−c2(signed reactive power)

S=S(apparent power)

  • U: RMS line-to-line voltage, in V.
  • I: RMS line current, in A.
  • c: cos φ, between 0 exclusive and 1 inclusive.
  • sign: +1 for inductive or −1 for capacitive.
  • P: active power in W.
  • Q: reactive power in var.
  • S: apparent power in VA. The factor 3 applies only to balanced three-phase operation.

Choosing voltage and circuit factor

CircuitVoltage to enterApparent power
Single-phaseAcross the load terminalsProduct U×I
Balanced three-phaseBetween phases3 times U×I
Sinusoidal resistive loadDepending on the circuitValue equal to P; Q is zero
U=400 V ; I=10 A ; cos(φ)=1U=400 VS=43 kVA ; P=43 kW ; Q=0
U=400 V ; I=10 A ; cos(φ)=0,8U=400 VS=43 kVA ; P=3,23 kW ; |Q|=2,43 kvar

Schneider Electric — active, reactive and apparent power ; NIST — Guide to the SI, Appendix B.9.

Worked examples

Example 1: 400 V, 20 A and cos(φ)=0,85

Apparent power is approximately 13,8564 kVA, active power 11,7779 kW and inductive reactive power 7,2993 kvar.

Example 2: Active load of 30 kW

At 400 V between phases and cos(φ)=0,90, current is approximately 48,11 A. Apparent power is 33,3333 kVA and inductive reactive power is 14,5297 kvar.

Example 3: Capacitive load of 10 kVA

The total apparent power is known and the behaviour is capacitive. The negative sign applies only to the reactive component; line current remains an RMS value, while active power retains the absorbed-energy convention.

S=10 kVA ; U=400 V ; cos(φ)=0,8 : I=10 000/(3×400)≈14,4338 A ; P=8 kW ; Q=−101−0,82=−6 kvar.

Assumptions and limitations

Balanced three-phase load; an unbalanced load requires a calculation for each phase. Steady-state sinusoidal operation. The displacement factor cos φ is not always the total power factor of a load with harmonics. Powers are absorbed and nonnegative except Q, whose sign is selected. No motor efficiency or starting current is derived.

Common mistakes

Enter the line-to-line voltage, typically 400 V on a 230/400 V supply, not the 230 V phase-to-neutral voltage. A motor’s mechanical power must first be divided by its efficiency. The sign of Q cannot be inferred from cos φ alone.

Frequently asked questions

Should 230 V or 400 V be entered?

Enter the line-to-line voltage. On a 230/400 V supply, it is 400 V; 230 V is the phase-to-neutral voltage.

What is the difference between kW, kvar and kVA in three-phase systems?

kW measures total active power, kvar signed reactive power and kVA apparent power S=3×U×I for a balanced system. Under sinusoidal conditions, S2=P2+Q2 and P/S=cos(φ). Active and apparent powers alone do not determine the sign of Q.

Does this apply to an unbalanced installation?

Not directly. Individual phase quantities are needed; this model does not calculate imbalance or neutral current.

Does star or delta change the line formula?

The balanced line formula is unchanged; winding voltage and current relations differ with connection.