Skip to content
Formulaxis

Electrical engineering

Power factor: calculating reactive power compensation in kvar

Find a load's power factor by dividing its active power by its apparent power. The second mode estimates, at constant active power, the capacitive kvar needed to raise the cos φ of a sinusoidal inductive load.

Created on , Revised on v2.0

Method and validation

Power factor: calculating reactive power compensation in kvar

Active power of the load under study, assumed constant during compensation.

Strictly positive apparent power, at least equal to P after unit conversion.

Initial values are examples.

Results

Power factor c
0.8dimensionless

Substitution in SI units

c=(50000 W)(62500 VA)=0.8

Compensation mode concerns a sinusoidal inductive load and a cos φ between 0 exclusive and 1 inclusive.

Reduce Q at constant active power

Power factor: calculating reactive power compensation in kvar · Power factor from P and STriangle on a shared scale: Q is the reactive component derived from P and S. The P/S ratio gives the power factor.P = 50 kWS = 62.5 kVAP / S = 0.8

Triangle on a shared scale: Q is the reactive component derived from P and S. The P/S ratio gives the power factor.

Illustrative diagram, not to scale.

Estimated reading time : 4 min · 700 words

Calculation details

In compensation mode, Q₁ and Q₂ are the inductive reactive demands before and after correction. Qc is the positive quantity to be compensated by a capacitive contribution, not a new active power.

01 · Power factor

FORMULA

c=PS

NUMERICAL SUBSTITUTION

c=(50 kW)(62.5 kVA)

RESULT

c=0.8

Power factor and compensation requirement

Power factor is the ratio of active power to apparent power. Under sinusoidal conditions, it equals the cosine of the phase shift. Capacitive compensation of an inductive load reduces the reactive power drawn upstream; the load's active power is assumed constant. Calculating kvar does not select a capacitor bank or its connection arrangement.

Formulas and symbols

Quantities are converted to consistent units before calculation.

c=PS(power factor)

Q1=P×tan(acos(c1))(initial reactive power)

Q2=P×tan(acos(c2))(reactive power at target)

Qc=P×(tan(acos(c1))−tan(acos(c2)))(required capacitive compensation)

  • P: active power in W.
  • S: apparent power in VA.
  • c: dimensionless power factor.
  • c₁ and c₂: initial and target cos φ; the target is at least equal to the initial value.
  • Q₁ and Q₂: inductive reactive powers before and after compensation, in var.
  • Qc: positive quantity of reactive power to be supplied by capacitive compensation. In the engine, c1 and c2 represent c₁ and c₂.

Example of compensation at constant active power

QuantityBeforeTarget
Active power50 kW50 kW
Cos φ0,750,95
Reactive powerAbout 44,10 kvarAbout 16,43 kvar
Difference to compensateAbout 27,66 kvarTheoretical capacitive contribution
Calculated apparent power50/0,75≈66,6667 kVA50/0,95≈52,6316 kVA

Schneider Electric — principles of power factor correction ; NIST — Guide to the SI, Appendix B.9.

Worked examples

Example 1: 50 kW for 62,5 kVA

The ratio of 50 to 62,5 gives a power factor of 0,8. On its own, it does not specify the direction of the phase shift.

Example 2: Raise 50 kW from 0,75 to 0,95

Reactive power decreases from about 44,10 kvar to 16,43 kvar. The theoretical compensation is about 27,66 kvar.

Example 3: Raise 18 kW from 0,80 to 0,92

The initial reactive power is 13,5 kvar and the target is about 7,67 kvar. Compensation is about 5,83 kvar.

Example 4: 120 kW workshop: improving cos φ from 0,78 to 0,95

Reactive power falls from 96,3 kvar to 39,4 kvar. The capacitor bank to install must therefore provide about 56,8 kvar, to be adjusted to the manufacturer’s steps and to the presence of harmonics.

Qc=P×(tan(φ1)−tan(φ2))=120×(tan(acos(0,78))−tan(acos(0,95)))=56,8 kvar.

Assumptions and limitations

Compensation mode concerns a sinusoidal inductive load and a cos φ between 0 exclusive and 1 inclusive. No capacitance in farads, frequency, voltage or connection arrangement is calculated. Harmonics, resonance, control and variable-load operation require a separate study. The P/S factor does not indicate the inductive or capacitive sign.

Common mistakes

Confusing power factor and efficiency mixes two balances: identify the powers being compared.

Entering mechanical power instead of active power gives incorrect reactive power: use electrical input power.

Taking the ratio as an indication of inductive behaviour hides ambiguity: specify the type of load.

Keeping a fixed capacitor bank with variable loads can overcompensate: study operating states.

Converting kvar to farads without voltage or frequency leaves the problem incomplete: specify the circuit.

Frequently asked questions

Is power factor the same as efficiency?

No. Power factor is P/S, while efficiency compares useful power with input power. Under sinusoidal conditions, P/S equals cos φ; with harmonics, this equality no longer holds in general.

Are kvar enough to select capacitors?

No. Voltage, frequency, connection arrangement, harmonic constraints, control and installation conditions must also be defined.

Why is active power held constant?

This comparison changes upstream reactive demand only; energy savings need a separate loss analysis.

What if target equals initial factor?

Compensation is zero, but the load may still require reactive power if the common factor is below one.